Amasethi ejeneretha abalulekile njengamandla ayisipele ezinhlelweni ezihlukene ezifana neziza zokwakha, imicimbi yangaphandle, izikhungo zenxanxathela yezitolo kanye nezakhiwo zokuhlala. Ukuqinisekisa ukuphepha, ikhwalithi nokuhambisana kwamasethi akhiqiza ugesi ahlangabezana nezindinganiso zamazwe ngamazwe.
AMANDLA E-JIANGSU LONGEN, ngokubambisana ne-SGS, izokwenza ukuhlolwa kwe-CE kujeneretha esethiwe ukuze kuqinisekiswe ukuhambisana nemithetho neziqondiso ze-European Union (EU)
1.Isampula yokuhlola
Isampula yejeneretha esethelwe lokhu kuhlolwa kwe-CE yi-LG-550
Amandla Ayinhloko:400KW/500KVA
Amandla Alindile:440KW/550KVA
Imvamisa:50Hz
Amandla kagesi:415V
Injini yomkhiqizo:Ama-Cummins
I-Alternator Brand:Stamford
2.Ukuhlolwa kwe-EMC
Amasethi e-generator ayimishini ye-electromechanical engakhiqiza ukuphazamiseka kwe-electromagnetic. Ukuhlolwa kwe-EMC kuhlola ikhono lejeneretha elisethiwe ukuze lisebenze ngaphandle kokubangela noma ukuphazanyiswa yizibuthe zikagesi.
2.1 Ukuhlola Ukukhishwa:
Ukuhlolwa okwenziwe futhi okunemisebe ngokuya ngamazinga afanaEN 55012:2007+A1:2009kuyisici esibalulekile sokuhlolwa kwe-CE kwamasethi ejeneretha.
Indlela Yokuhlola:CISPR 12:2007+A1 2009
Ibanga Lemvamisa:30MHz ukuya ku-1GHz
Ibanga lokulinganisa: 3m
Indawo yokusebenza:
Izinga lokushisa:22 ℃
Ukuswakama:50% RH
I-Atmospheric Pressure: 1020 mbar
Idatha yokulinganisa:
Ukuskena kwangaphambilini kokuqala kwenziwa ekamelweni kusetshenziswa i-spectrum analyzer kumodi yokuthola inani eliphakeme.Izilinganiso ze-Quasi-peak zenziwa ngokusekelwe kugrafu yokushanela ephezulu.I-EUT ikalwe ngothi lwe-BiConiLog olunama-polarities angu-2 omgogodla.
2.2 Ukuhlolwa Kokuzivikela
Ngaphezu kwalokho, ukuhlolwa kokuzivikela komzimba kuqinisekisa ukuthi isethi yejeneretha ingakwazi ukumelana nezimo zangaphandle ze-electromagnetic ngaphandle kokuwohloka kokusebenza.EN 61000-6-2:2019izindinganiso
Ibanga Lemvamisa:80MHz ukuya ku-1GHz, 1.4GHz ukuya ku-6GHz
I-Antenna Polarisation:Iqondile futhi Ivundlile
Ukuguquguquka:1kHz, 80% Amp. Mod, 1% ukukhuphuka
Imiphumela:Akukho ukwehliswa kokusebenza kwe-EUT okuboniwe.
2.3 Ukuhlola Ukukhipha I-Electrostatic
Ukukhipha Impedance:330Ω/150pF
Inombolo Yokukhishwa:Ubuncane bezikhathi eziyi-10 endaweni ngayinye yokuhlola
Imodi yokukhipha:Ukukhipha Okukodwa
Isikhathi Sokukhipha:Ubuncane besekhondi elingu-1
Imiphumela:
Akukho ukwehliswa kokusebenza kwe-EUT okuboniwe.
3.MD Directive Test
Ukuhlolwa kokuphepha kukagesi: Okunye kokuqukethwe okuyinhloko kokuhlolwa kwe-CE kwamasethi ejeneretha ukuphepha kukagesi. Lokhu kuhilela ukuhlola ukwakheka nokwakhiwa kwesethi yejeneretha ukuze kuqinisekiswe ukuvikeleka ezingozini zikagesi. Inqubo yokuhlola ihlanganisaukuhlolwa kokumelana ne-insulationnezinye izivivinyo zokusebenza zesethi yejeneretha. Ukuhambisana nezindinganiso ezifanaI-EN ISO8528-13futhiI-EN ISO12100kubalulekile ukuhlangabezana nezidingo zokuphepha zikagesi.